Tuesday 3 January 2017

9.7 DEGASSING OF CYLINDERS



                Work on LPG cylinders shall not be carried out in the enclosed space prior to degassing.

             Degassing should be carried out in CCOE approved site.  Cylinders shall  be degassed by purging the same by inert gas, steam or by filling water till it overflows.  The water shall be retained in the cylinders for not less than one hour to ensure that entire vapour or gas remaining in the cylinder comes out.  After emptying out the water, the cylinders shall be kept in inverted position and be tapped gently by non-metallic hammer to remove dust, rust or any loose remnants in the cylinders.

               
              After degassing, the inside of the cylinders shall be checked by an Explosimeter to ensure that the cylinders are gas-freed and shall again be taken up for de-gassing till it completely gas freed.